14-2
TROUBLESHOOTING
SM DNGRPM 1-E.4 GB
ATTENTION : check for broken or loose cable lugs first
NO SYMPTON PROBABLE CAUSE CORRECTIVE ACTION
9.
Only indoor fan and
compressor working.
Outdoor fan blocked. - Remove obstructions.
10.
Only indoor fan
working.
-Run capacitor of outdoor
fan motor faulty. -Windings of
outdoor fan are shorted.
- Replace capacitor. -Replace motor.
11.
No cooling or heating
takes place, indoor and
outdoor fans working.
- Overload safety device on
compressor is cut out (low
voltage or high temperature)
- Compressor run capacitor
faulty. - Compressor windings
are shorted.
- Check for proper voltage, switch off
power and try again after one hour. -
Replace compressor capacitor. - Replace
compressor.
12.
No air supply at indoor
unit, compressor
operates.
-Indoor fan motor is blocked
or turns slowly. -indoor fan
run capacitor faulty. -motor
windings are shorted.
- Check voltage, repair wiring if
necessary. -Check fan wheel if it is
tight enough on motor shaft, tighten if
necessary. -Replace indoor fan motor.
13.
Partial, limited air
supply at indoor unit.
Lack of refrigerant (will
accompanied by whistling
noise) cause ice formation on
indoor unit coil in cooling mode.
-Charge the unit after localizing leak.
14.
Water accumulates and
overflow from indoor
unit section.
Drain tube or spout of drain pan
clogged.
-Disassemble plastic drain tube from
spout of indoor unit drain pan.
15.
Water dripping from
outdoor unit base. (in
heating mode)
Water drain outlet is clogged.
-Open outdoor unit cover clean out water
outlet clean the base inside througly.
16.
Freeze-up of outdoor
coil in heating mode,
poor heating effect
in room, indoor fan
operates.
-Faulty outdoor thermistor. -
Faulty control cable. - Outdoor
temperature is too low (below
-2°C) -Outdoor unit air outlet is
blocked.
-Replace thermistor. - Repair control
cable. - Shut unit off, outdoor temp. is
below design conditions and cannot
function properly. -Remove obstructions.