CONTROL SYSTEM
SM DNGRPM 1-E.4 GB
d. STEP 3: AUTO LED WALK TEST.
1) All the LEDS will turn OFF.
2) All the LEDS will turn ON for 1 second one by one in the following sequence:
STAND-BY Ö OPERATE Ö TIMER Ö FILTER Ö COOL Ö HEAT.
3) In PRX all the LEDS will turn ON for 1 second one by one in the following
sequence : 18 °c Ö 20 °c Ö 22 °c Ö 24 °c Ö 26 °c Ö 28 °c Ö 30 °c Ö
High IFAN Ö Auto IFAN Ö Med IFAN Ö Low IFAN Ö STAND-BYÖ TIMER Ö
FILTER ÖCOOLÖ HEAT.
e. STEP 4: AUTO REALY WALK TEST:
All relays will energize one by one in the following sequence:
COMPRESSOR Ö OUTDOOR FANÖR. V. Ö HEATER 1 Ö HEATER 2 Ö
INDOOR WATER PUMP Ö SWING or OUTDOOR WATER PUMP Ö INDOOR
FAN: LOW Ö MID Ö HIGH.
When the relay walk test is completed, the next test will start automatically.
f. STEP 5: FREQUENCY TESTING:
If the frequency measuring process fails the COOL LED will turn ON. In order to
move to the next step, press ON/OFF button on the remote control.
g. STEP 6: INPUT TEST.
The test purpose is to check the analog real time indicators (thermistors, LEVEL
and clock) according to the table below.
LED Indicator Condition for LED to be ON
STBY LED
Room thermistor 25°c
OPER LED
Indoor coil thermistor 25°c
TIMER LED
Outdoor coil thermistor 25°c
FILTER LED Clock
COOL LED LEVEL 2&3
HEAT LED LEVEL 4
h. STEP 7: TIMING RESET TEST (WATCH DOG).
The test purpose is to verify that the CPU rise time after power failure is between 1
to 3 sec, test results are indicated on the LEDS : STAND-BY,OPER, TIMER and
FILTER turning ON one by one.
The results of the test are coded as follows:
Pass condition:
1 sec - STAND-BY and OPER are turned ON
2 sec - STAND-BY, OPER and TIMER are turned ON