Electra OU10-36 ST Service Manual Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 160
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
5-19
PERFORMANCE DATA & PRESSURE CURVES
SM DNGRPM 1-E.4 GB
5.15 DNG 44 / OU10-42 R410A
5.15.1 Cooling Capacity (kW)
Entering Air DB
OD Coil(
o
C)
Data
Entering Air WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC 12.86 13.32 13.63 13.96 14.17
SC 8.70 9.07 9.42 9.66 9.84
PI 3.08 3.08 3.09 3.10 3.11
20
(1)
TC 12.44 13.11 13.53 13.85 14.15
SC 8.52 8.98 9.36 9.63 9.81
PI 3.34 3.35 3.36 3.38 3.39
25
TC 11.77 12.71 13.36 13.77 14.10
SC 8.31 8.81 9.29 9.56 9.74
PI 3.61 3.64 3.66 3.68 3.71
30
TC 11.01 11.99 12.95 13.41 13.81
SC 8.04 8.55 9.09 9.36 9.53
PI 3.89 3.95 3.99 4.02 4.05
35
TC 10.19 11.06 12.20 12.81 13.42
SC 7.65 8.20 8.88 9.14 9.32
PI 4.20 4.27 4.34 4.37 4.40
40
TC 9.27 10.09 11.01 12.04 12.66
SC 7.21 7.76 8.40 8.67 8.84
PI 4.53 4.60 4.68 4.74 4.78
46
TC 8.04 8.79 9.67 10.68 11.51
SC 6.64 7.11 7.66 7.93 8.10
PI 4.95 5.02 5.14 5.21 5.27
LEGEND
TC Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)
DB Dry Bulb Temp., (
o
C)
ID Indoor
OD Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 16).