Electra OU7-24 RC Service Manual Page 160

  • Download
  • Add to my manuals
  • Print
  • Page
    / 168
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 159
12
Outdoor
unit
Gas-side
Indoor unit
Trap
Liquid side
Pipe joint
Chart 25
Chart 26
Manifold value
Multi-meter Pressure meter
-76CmHg
Lo-lever
Hi-lever
Charge hose
Charge hose
Vacuum
pump
Lo-lever
Chart 27
Joint nut
Quadrangle-cover
Chart 28
Trap body
Repair mouth
System joint
Quadrangle-lever
Linking pipe joint
Chart 29
Check-point of
indoor unit
Check-point of
outdoor unit
1) ON operation: Take off quadrangle cover,
clip the quadrangle head with a wrench
and turn it anticlockwise to the end. Then
fasten the quadrangle cover.
2) OFF operation: The operation is the same
as the ON operation, but you should turn
it clockwise this time.
7. Disassemble the charge hose from the repair-mouth of stop value A, and fasten the unit.
Operate the stop valves
Open the value stem until it reaches the limitator. Do not open it any further.
Fasten the stop values with a wrench or such tools.
The wrench torque is listed in the Table 2 mentioned above.
CAUTIONS
All the stop values should be opened before test operation. Each air conditioner has two stop values of
different sizes on the side of the outdoor unit, which operate as Lo-stop value and Hi-stop value;
respectively .The ON/OFF operation is described in the left chart. (Refer to Chart 28)
CHECK THE LEAKAGE
Check all the joints with the leak detector or soap water. (refer to Chart 29)
NOTE: in the chart
A ............... Lo-stop value
B ............... Hi-stop value
C,D ........... Joints of the connecting pipe
to the indoor unit .