Electra OU7-24 RC Service Manual Page 38

  • Download
  • Add to my manuals
  • Print
  • Page
    / 168
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 37
5-21
PERFORMANCE DATA & PRESSURE CURVES
Revision Y06-02Service Manual - KN Series
5.15 KN45 / OU10-47T R410A
5.15.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
13.02 13.48 13.80 14.13 14.34
SC
8.17 8.52 8.85 9.07 9.24
PI
3.12 3.13 3.13 3.14 3.16
20
(1)
TC
12.59 13.27 13.69 14.02 14.32
SC
8.00 8.44 8.80 9.05 9.21
PI
3.39 3.40 3.41 3.43 3.43
25
TC
11.92 12.87 13.53 13.94 14.28
SC
7.80 8.28 8.73 8.98 9.15
PI
3.66 3.69 3.71 3.73 3.76
30
TC
11.14 12.13 13.11 13.57 13.98
SC
7.55 8.03 8.54 8.79 8.95
PI
3.95 4.01
4.04
4.07 4.11
35
TC
10.32 11.20
12.35
12.97 13.58
SC
7.18 7.70 8.34 8.58 8.75
PI
4.26 4.33
4.40
4.43 4.46
40
TC
9.38 10.21
11.14
12.19 12.81
SC
6.77 7.29 7.89 8.14 8.31
PI
4.59 4.66 4.74 4.80 4.85
46
TC
8.14 8.90 9.79 10.81 11.65
SC
6.24 6.68 7.19 7.44 7.61
PI
5.02 5.09 5.21 5.28 5.34
LEGEND
TC Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)
DB Dry Bulb Temp., (
o
C)
ID Indoor
OD Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).