5-7
PERFORMANCE DATA & PRESSURE CURVES
Revision Y06-02Service Manual - KN Series
5.6 KN30 / OU8-30T R410A
5.6.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
8.75 9.06 9.27 9.49 9.64
SC
5.88 6.13 6.37 6.53 6.65
PI
2.03 2.03 2.04 2.04 2.05
20
(1)
TC
8.46 8.92 9.20 9.42 9.62
SC
5.76 6.07 6.33 6.51 6.63
PI
2.20 2.21 2.22 2.23 2.23
25
TC
8.01 8.65 9.09 9.37 9.59
SC
5.61 5.95 6.28 6.46 6.58
PI
2.38 2.40 2.41 2.43 2.44
30
TC
7.49 8.15 8.81 9.12 9.39
SC
5.43 5.78 6.14 6.32 6.44
PI
2.57 2.60
2.63
2.65 2.67
35
TC
6.93 7.52
8.30
8.72 9.13
SC
5.17 5.54 6.00 6.17 6.29
PI
2.77 2.81
2.86
2.88 2.90
40
TC
6.31 6.86
7.49
8.19 8.61
SC
4.87 5.24 5.68 5.86 5.98
PI
2.99 3.03 3.08 3.12 3.15
46
TC
5.47 5.98 6.58 7.27 7.83
SC
4.49 4.81 5.18 5.36 5.48
PI
3.26 3.31 3.39 3.43 3.47
LEGEND
TC Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)
DB Dry Bulb Temp., (
o
C)
ID Indoor
OD Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).